Pingxiang Daier Separation Tech Sep 12, 2026

How to Measure Liquid Distributor Flow Uniformity with a Catch-Pan Test

How to Measure Liquid Distributor Flow Uniformity with a Catch-Pan Test

A liquid distributor should not be accepted only because every outlet appears to discharge liquid. The relevant question is whether the measured flow is sufficiently uniform across the tower area and whether any systematic dry or overloaded zones exist.

A catch-pan test converts visual observation into measurable distribution data.

What a Catch-Pan Test Measures

Containers are positioned beneath individual outlets or defined collection zones. After the distributor reaches stable operation, liquid is collected for a fixed period and the volume or mass in each container is recorded.

The test can identify:

Outlet-to-outlet flow variation

Completely dry outlets

Overloaded areas

Radial or circumferential bias

High flow near the feed inlet

Low flow at distant trough ends

Effects of distributor tilt

Repeated patterns caused by panel geometry

The collection layout must match the purpose of the test. Measuring several large quadrants may identify gross zonal maldistribution but hide individual blocked or oversized outlets.

Normalize Unequal Collection Areas

If all containers represent the same tower area, their collected quantities can be compared directly. When collection zones have different areas, use area-normalized liquid flux:

Liquid fluxᵢ = collected flowᵢ ÷ represented areaᵢ

Without this correction, a larger collection zone will appear overloaded even if its irrigation rate per unit area is correct.

The total collected flow should also be compared with the measured distributor inlet flow. A poor mass balance may indicate splashing, leakage, incomplete capture or measurement error.

Calculate the Coefficient of Variation

A common indicator is the coefficient of variation:

CV = standard deviation of local liquid flow ÷ mean local liquid flow × 100%

A lower CV generally indicates more uniform point-to-point flow. However, CV alone cannot describe where the deviations occur.

Two distributors may have the same CV:

One has small random differences scattered across the tower.

The other has one large dry zone and one overloaded zone.

The second pattern is normally more damaging because packing cannot quickly correct large-scale zonal maldistribution.

Record Spatial Patterns, Not Just One Number

Each measurement should be linked to its physical position. A distribution map can reveal:

A low-flow ring near the shell

High flow under the feed box

One weak distributor panel

A tilted trough

Alternating high and low laterals

Leakage through panel joints

Liquid migrating along the underside

Photographs and a numbered collection grid make later troubleshooting much easier.

Test the Required Operating Range

A distributor that is uniform at normal flow may fail at minimum flow because liquid head becomes too low. At maximum flow it may overflow, splash or exceed its intended operating level.

The test plan should therefore include, where required:

Minimum operating flow

Normal design flow

Maximum operating flow

Transitional flow where a second row of outlets begins operating

Drain-down condition

Allow the distributor level and discharge pattern to stabilize before beginning each timed collection.

Control the Test Conditions

Record:

Test-liquid temperature

Density and viscosity

Total inlet flow

Inlet pressure

Distributor levelness

Liquid depth

Collection time

Container calibration

Outlet configuration

Any temporary test piping

The feed arrangement should reproduce the intended inlet direction and momentum as closely as practical. A temporary hose aimed at one trough can create a false failure that will not exist with the final feed pipe.

Define Acceptance Before Testing

There is no single universal CV or point-flow tolerance suitable for every distributor and process. Acceptance depends on:

Packing type

Required separation efficiency

Distributor style

Drip-point density

Tower diameter

Liquid load

Turndown

Sensitivity to wall flow

Test accuracy

The purchase specification should define the permitted statistical variation, allowable individual deviation, treatment of dry points and zonal acceptance criteria before fabrication begins.

Investigate the Cause of Every Pattern

When a test fails, do not immediately enlarge or plug outlets. First check:

Hole dimensions

Burrs and outlet orientation

Plugging

Panel levelness

Trough straightness

Feed-box performance

Joint leakage

Pressure variation

Liquid crawling under the distributor

Correcting one outlet changes the total hydraulic balance and may create a new problem elsewhere.

Required Test Report

A useful report should contain:

Distributor identification

Approved drawing revision

Test arrangement

Inlet-flow calibration

Raw measurements

Area-normalized results

Mean flow and CV

Minimum and maximum point flow

Spatial distribution map

Photographs

Nonconformities and retest results

A catch-pan test is valuable because it changes “the distributor looks even” into traceable engineering evidence.

 

Why Feed Piping Should Not Load the Liquid Distributor

How to Design Removable Access Panels in Tower Internals